The following values of full-load currents are motors running at usual
speeds and motors with normal torque characteristics.
The voltages listed are rated motor voltages. The currents listed shall
be permitted for system voltage ranges of 110 to 120, 220 to 240 volts.
Table 430.250 Full-Load Currents in Amperes, Three-Phase
Alternating-Current Motors
Horsepower115
Volts
200
Volts
208
Volts
230
Volts
460
Volts
575
Volts
2300
Volts
1/24.42.52.42.21.10.9
3/46.43.73.53.21.61.3
18.44.84.64.22.11.7
1-1/2126.96.66.03.02.1
213.67.87.56.83.42.7
31110.69.64.83.9
517.516.715.27.66.1
7-1/225.324.222119
1032.230.8281411
1548.346.2422117
2062.159.4542722
2578.274.8683427
309288804032
401201141045241
501501431306552
60177169154776216
75221211192967720
1002852732481249926
12535935331215612531
15041439636018014437
20055252848024019249
25030224250
30036128972
35041433683
40047738296
NEC is a registered trademark of the National Fire Protection Association, Inc. All NEC references by Electrical Helper are interpretations of the NEC by the Electrical Helper staff and are not NEC statements. The official position of the NEC requires that the NEC be referred to in its entirety.
Article 430.22 (A) states conductors supplying a single motor used in a continuous duty application shall have any less than 125 percent of the motors full load current rating determined by 430.6 (A)(1)

See Article 430.6 (A)(1) in the NEC for exceptions and referring tables.