230 Volt 1 Phase 10HP

Thermal Magnetic Breaker Size90Amp
Dual Element Time-Delay Fuse60 Amp
Manual Motor Starter45-63 Amp
IEC Contactor Size65 Amp
NEMA Rated Starter Size3
Notice:
NEC is a registered trademark of the National Fire Protection Association, Inc. All NEC references by Electrical Helper are interpretations of the NEC by the Electrical Helper staff and are not NEC statements. The official position of the NEC requires that the NEC be referred to in its entirety.
Table 430.248 Full-Load Currents in Amperes, Single-Phase.
Alternating-Current Motors
The following values of full-load currents are typical for
motors running at speeds usual for belted motors and
motors with normal torque characteristics.
The voltages listed are rated motor voltages. The currents
listed shall be permitted for system voltage ranges of
110 to 120, 220 to 240, 440 to 480, and 550 to 600

Single Phase Motor Data
For Standard Squirrel Cage 60 Hz 1800 RPM Motors
115200208230
HorsepowerVoltVoltVoltVolt
1/29.85.65.44.9
3/413.87.97.66.9
1169.28.88
1-1/22011.51110
22413.813.212
33419.618.717
55632.230.828
7-1/280464440
1010057.55550