230 Volt 1 Phase 10HP
Thermal Magnetic Breaker Size | 90Amp |
Dual Element Time-Delay Fuse | 60 Amp |
Manual Motor Starter | 45-63 Amp |
IEC Contactor Size | 65 Amp |
NEMA Rated Starter Size | 3 |
Notice: |
NEC is a registered trademark of the National Fire Protection Association, Inc. All NEC references by Electrical Helper are interpretations of the NEC by the Electrical Helper staff and are not NEC statements. The official position of the NEC requires that the NEC be referred to in its entirety. |
Table 430.248 Full-Load Currents in Amperes, Single-Phase. Alternating-Current Motors |
The following values of full-load currents are typical for motors running at speeds usual for belted motors and motors with normal torque characteristics. |
The voltages listed are rated motor voltages. The currents listed shall be permitted for system voltage ranges of 110 to 120, 220 to 240, 440 to 480, and 550 to 600 |
Single Phase Motor Data |
For Standard Squirrel Cage 60 Hz 1800 RPM Motors |
115 | 200 | 208 | 230 | |
Horsepower | Volt | Volt | Volt | Volt |
1/2 | 9.8 | 5.6 | 5.4 | 4.9 |
3/4 | 13.8 | 7.9 | 7.6 | 6.9 |
1 | 16 | 9.2 | 8.8 | 8 |
1-1/2 | 20 | 11.5 | 11 | 10 |
2 | 24 | 13.8 | 13.2 | 12 |
3 | 34 | 19.6 | 18.7 | 17 |
5 | 56 | 32.2 | 30.8 | 28 |
7-1/2 | 80 | 46 | 44 | 40 |
10 | 100 | 57.5 | 55 | 50 |